Capacity |
6kVA / 5.4kW |
10kVA / 9kW |
|
Input |
|
|
|
Phase |
3 Phase 4 Wires and Ground or Single Phase & Ground |
|
Rated Voltage |
380/400/415Vac or 220/230/240VAC |
|
Voltage Range |
208~478Vac or 120VAC-276VAC |
|
Frequency Range |
40Hz-70Hz |
|
Power Factor |
≥0.99 |
|
Current THDi |
≤5% (100% Nonlinear Load) |
|
Bypass Voltage Range |
Max. Voltage: +15% (Optional +5%, +10%, +25% ) Min. Voltage: -45% (Optional -20%, -30%) |
|
Frequency Protection Range: ±10% |
|
ECO Range |
Same As The Bypass |
|
Generator Input |
Support |
|
Output |
|
|
Phase |
Single Phase & Ground |
|
Rated Voltage |
220/230/240VAC |
|
Power Factor |
0.9 |
|
Voltage Regulation |
±2% |
|
Frequency |
Utility Mode |
±1%, ±2%, ±4%, ±5%, ±10% of The Rated Frequency (Optional) |
|
Battery Mode |
(50±0.2) Hz |
|
Crest Factor |
3:1 |
|
THD |
≤2% With Linear Load; ≤5% With Non-linear Load |
|
Waveform |
Pure Sinewave |
|
Efficiency |
ECO Mode 97%; Normal Mode 90% |
|
Battery |
|
|
Voltage |
Standard: 192Vdc; Optional Voltage: 216/240Vdc |
|
Backup Time |
Full Load 2min( Standard), Long Time Unit Depends on The Capacity of External Batteries |
|
Estimated Remaining Time Displayed on the LCD |
|
Recharge Time to 90% |
8~10 Hours (Standard) |
|
Charging Current |
Maximum Current 6A; Charge Current can be Set According to Battery Capacity Installed. |
|
Battery Socket |
Hardwire |
|
Transfer Time |
Utility to Battery : 0ms; Utility to Bypass: 0ms |
|
Protection |
|
|
Overload |
AC Mode |
Load 110%: Last 90S, 125%15S: Last 30S, 150%: Last 0.5S, 150% Shut Down UPS Immediately |
|
Bat. Mode |
Load 110%: Last 15S, 125%: Last 0.5S, 150%: Last 1250ms, 150% Shut Down UPS Immediately |
|
Bypass Mode |
40A (Input Breaker) |
60A (Input Breaker) |
|
Short Circuit |
Hold Whole System |
|
Overheat |
Line Mode: Switch to Bypass; Backup Mode: Shut Down UPS Immediately |
|
Battery Low |
Alarm and Switch off |
|
Self-Diagnostics |
Upon Power On and Software Control |
|
EPO (Optional) |
Shut down UPS Immediately |
|
Battery |
Complies with EN62040-2 |
|
Alarms |
|
|
Audible & Visual |
Line Failure, Battery Low, Overload, System Fault |
|
Display |
|
|
Status LED & LCD |
Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault |
|
Reading on the LCD |
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner |
|
Temperature & Remaining Battery Backup Time |
|
Physical |
|
|
Dimension (W×D×H) (mm) |
443×131(3U)×580 |
|
Weight (kg) |
23 |
25 |
|
Input Connection |
Hardwire |
|
Output Connection |
Hardwire |
|
External Battery Connection |
Hardwire |
|
Comunication Interface |
USB (Optional) , RS485 (Optional) , Parallel Port (Optional) , SNMPCard (Optional) ,Centralized Monitoring Card (Optional) |
|
Environment |
|
|
Operating Temperature |
0~40°C |
|
Storage Temperature |
-25°C~55°C |
|
Humidity |
0%~95% (Non-Condensing) |
|
Altitude |
<1500m |
|
Safeity Conformance |
CE,EN/IEC 62040-2,EN/IEC 62040-1-1 |