Model |
|
|
|
|
Capacity |
1kVA / 900W |
2kVA / 1800W |
3kVA / 2700W |
|
Input |
|
|
Rated Voltage |
208V / 220V / 230V / 240VAC |
|
Voltage Range |
Half Load (110-300) ± 5VAC; Full Load (160-300) ± 5VAC |
|
Frequency |
40/70Hz (Auto Sensing) |
|
Power Factor |
≥0.98 |
|
Bypass Voltage Range |
Rated Output Voltage -34V ~Rated Output Voltage +32V |
|
Output |
|
|
Voltage |
208V/220V/230V/240 VAC Setting Available Via LCD |
|
Voltage Regulation |
± %1 |
|
Frequency |
45-55Hz or 55-65Hz (Synchronized Range); 50/60 ± 0.2Hz (Battery Mode) |
|
Waveform |
Pure Sine Wave |
|
Krest Factor |
3:1 |
|
Harmonic Distortion |
≤ %2 (Lineer Load) |
≤ %5 (Non-Lineer Load) |
|
Transfer Time |
AC Mode To Battery Mode:0 ms |
|
Overload Capacity |
105%-150%: Transfer to Bypass after 20s |
>150%: Transfer to Bypass After 150 ms |
|
Efficiency |
|
|
AC Mode |
≥%90 |
|
Battery Mode |
≥%87 |
|
ECO Mode |
≥%94 |
|
Battery |
|
|
DC Voltage |
24 VDC |
48 VDC |
72 VDC |
|
Inbuilt Battery of Standard Mode |
2 x 12V 9Ah |
4 x 12V 9Ah |
6 x 12V 9Ah |
|
Charge Current |
Standard Model |
1A |
Long Time Model |
6A |
|
Typical Charge Time |
8 Hours Recover to 90% Capacity |
|
Alarm |
|
|
Utility Failure |
Beep/4s |
|
Battery Low |
Beep/1s |
|
Overload |
Beep Twice/1s |
|
UPS Fault |
Long Beep |
|
Physical Features |
|
|
Dimension (mm) WxDxH |
144 x 410 x 215 |
190 x 452 x 341 |
|
Packing Dimension (mm) WxDxH |
231 x 492 x 316 |
320 x 550 x 462 |
|
Net Weight (kg) |
13.0 |
23.5 |
26.6 |
|
Gross Weight (kg) |
14.5 |
25.0 |
28.8 |
|
Environment |
|
|
Humidty |
20~%90 RH @ 0~40 ºC (non-condensing) |
|
Nise Level |
≤ 45dB (1m) |
|
Management |
|
|
Standart RS232, Opsiyonel USB-SNMP |
Support Windows 98/2000/2003/XP/Vista/2008/Windosws 7/8 |
|
Optional SNMP |
Power Management From SNMP Manager and Web Browser |