Model |
|
|
|
|
|
Capacity |
400 kVA
|
500 kVA |
600 kVA
|
800 kVA |
|
Power Watt |
320 kW
|
400 kW |
480 kW
|
640 kW |
|
Input |
|
|
Input Voltage Range |
220/380VAC -15% +18% 3P+N+PE Optional 220/380VAC -37% +22% 3P+N+PE |
|
Input Power Factor |
At Full Load >0.99 |
|
Input Frequency Range |
45 - 65 Hz (Selectable) |
|
Rectifier |
IGBT |
|
THDi |
<%3 |
|
Output |
|
|
Output Voltage Range |
220/380VAC, 230/400VAC and 240/415VAC 3 Phase + N ± 1% |
|
Recovery |
0% - 100% - 0% Load, Maximum Output Tolerance 5%, 1% Back to Band <40ms |
|
Efficency |
Up to 93%, Eco Mode 98% |
|
Output Frequency Range |
50Hz ±0.5% Synchronous With the Network / 50Hz ±0.01% Battery Mode |
|
Output THD |
Lineer Load <%2
Non-lineer Load <%5 |
|
Crest Factor |
3:1 |
|
Overload Capacity |
At 125% Load 10min, at 150% Load 1min |
|
Battery |
|
|
Quantity (12V DC VRLA) |
2x31 |
|
Charge Value (C) |
Nominal 0,1 C, Adjustable |
|
Battery Power |
25% of The Device Power |
|
Internal Battery |
Not Available |
|
Communication |
|
|
Communication Port |
RS232 Standart, RS485 ve SNMP Adapter Option |
|
Dry Contact |
Optional |
|
Protocol |
SEC, TELNET |
|
Standards |
|
|
Quality |
ISO 9001 - ISO 14001 - ISO 18001 |
|
Performance |
EN62040 -3 (VFI-SS-111) |
|
EMC/LVD |
EN62040 - 2 / EN62040 -1 EN60950 |
|
General |
|
|
Running Temperature |
For UPS 0°C~40°C For Battery 0°C~25°C |
|
Storage Temperature |
For UPS 15°C ~45°C For Batteries -10°C~60°C |
|
Protection Class |
IP20 |
|
Chassis |
Anti-Static Paint Protection |
|
Humidity |
0-95% |
|
Altitude |
<1000m, Correction Factor 1. <2000m, Correction Factor >0.92, <3000m; Correction Factor >0.84 |
|
Alerts |
500 Event Log |
|
Paralel Operation |
Parallel Power Increase up to 16pcs. |
|
EPO (Emergency Power Off) |
Standard |
|
Isolation Transformer |
Optional |
|
Net Weight (without battery) |
850 |
1350 |
1400 |
1950 |
|
|
Dimensions (WxDxH) |
1250 x 815 x 1905 |
1830x850x2010 |
3400x815x1905 |
|
|
Makelsan reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Makelsan products previously or subsequently sold. Makelsan does not guarantee the items of the accuracy and completeness. |